Product News

New and original Pepperl+Fuchs solenoid driver KFD2-SL2-Ex1 arrived.

News April 13, 2020

Feature: 1-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508.


Pepperl+Fuchs Intrinsic Safety Barriers K-System Solenoid Driver KFD2-SL2-Ex1.


General specifications

Signal type: Digital Output    


Functional safety related parameters

Safety Integrity Level (SIL): SIL 2  


Function: KFD2-SL2-Ex1

This isolated barrier is used for intrinsic safety applications.

The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area.

It is controlled via logic signals. The inputs have two defined states: 1-Signal = 16 V DC ... 30 V DC, 0-Signal = 0 V DC ... 5 V DC. The current consumption of the input is about 3 mA.

At full load, 11.7 V at 45 mA is available for the hazardous area application.

If the field impedance is > 10 kΩ for lead breakage or < 50 Ω for short circuits a line fault is detected.

A fault is signalized by LEDs and a separate collective error message output.


Associated Products:

KFD2-EB2

KFD2-EB2.R4A.B

UPR-03

UPR-03-S

KFD2-EB2.R4A.B.SP

KFD2-EB2.SP

UPR-03-M

K-DUCT-BU

K-DUCT-BU-UPR-03


Pepperl-Fuchs KFD2-SL2-Ex1

Legal Disclaimer

Wuhan Sunup Industrial Equipment Co., Ltd. is not an authorized dealer, agent or affiliate of any of the brands or manufacturer, the products of which are offered for sale on www.sunupauto.com. All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the rights of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All products are 100% original, genuine and legally purchased from authorized sources. more >